1. Technical specification

    Voltage : 208V ~ 480V

    Frequency : 60Hz / 50Hz

    Phase connection : 3 Phase Y & Delta connection

    PF improved : More than 0.95

    compensation speed : 4~16msec

    Running condition : 25℃ (Recommend)  Max 40℃ ~  Min -10℃, Altitude 1000M 

2. General specification

      1) SCR use Zero crossing function and do not make inrush current.

      2) Controller display 1 ~63th harmonic information on LCD.

      3) SVC use same Q'ty capacitor bank and switching module. Each system must

         running separately if one SCR is broken do not effect to other module.    

      4) CT location is up to engineer. support Closed-loop & Open-loop

      5) Switching module must has LED and show module’s status.

      6) SVC basic function : Alarm for switching module over heat, Alarm for reactor over heat,

         Resonance, Phase reverse, low voltage, Over voltage. SVC support self-checking

         functionfor SCR and Capacitor.

      7) Controller show each Phase voltage and current waveform.

      8) Controller show capacitor working time and support capacitor changing term.

      9) Controller can be set Capacitor working time and make all capacitor working in same

         working time.

      10) Controller show capacitor's compensate KVAR and support Electricity cost.

      11) Engineer can be set the Re-start time for reactor over heat and heat sink over heat.

3. SVC CONTROLLER            

         A. Controller input power : 220VAC

         B. Input power   : 100~480V 60HZ (R, S, T, N 4line input)

         C. Input current  : CT 5 ea (Main R,S,T & Capacitor feed back 2ch)

         D. CT Ratio : 5/5~10,000/5A

         E. Response time              : 4~16msec

         F. Setting function            : Capacitor Bank(1~12Bank), Bank combine,

                                 Capacitor Running Time Limit

                         Phase system selecting (3phase Wye or Delta),

                         Rated voltage

                         Over-Voltage(100~150%),  Under-Voltage(50~100%),

                         CT ratio(main/Capacitor bank),

                         Running way (Auto/Manual/Test mode)

                         Time, display re-flash                  

         G. Protection function      : Resonance (Rated voltage 150% , Phase reverse, lost

                         phase, limit running time,Low/Over voltage, Over-temperature, SCR error

         H. LCD Display    : 240 * 128 Graphic LCD

4. LCD Display

              - Load side : Accumulate running time, Accumulate KW,

                         Accumulate KVA, Accumulate PF

                         KW (total), KVAR(total);

                         KVA(total), Present PF (total),

                         Voltage (Each Phase), Current (Each Phase), Frequency

                         V_thd(Each Phase), I_thd(Each Phase),

                         Harmonic  Spectrum, Current Waveform

 

              - Source side : KW (total), KVAR (total), KVA (Total), Present PF (Total),

                         Voltage (Each Phase), Current (Each Phase)

                         V_thd(Each Phase), I_thd(Each Phase),

                         Harmonic Spectrum, Current Waveform

 

              - Capacitor side : Accumulate compensate KVAR, KW, Average PF

                              Each Capacitor Bank accumulate running time

                              Voltage (Each Phase), Current (Each Phase) V_thd, 

5. SCR Switching Module

         A. Control power  : 220VAC 60㎐

         B. SWITCHING material : SCR

         C. Rated current : 3¢ 200A

         D. Control Input : Digital method (Controller Output)

         E. Cooling : Air cooling by FAN

         F. Temperature Sensor :  55℃(alarm),  85℃(SVC stop)

         G. Bank Q'ty : 1Bank

         H. Indicate : Power status, SCR running status LED

 6.  Series Reactor

         A. Running Voltage   : AC600V or Customer request

         B. Rated capacity   : 7% of Capacitor capacity or customer request

         C. Winding       : Enamel Coating  "H" class (180℃)

         D. TYPE       : DRY, Low loss type. Self-recovering type.

B2B Trade

Price (FOB) Negotiable transportation -
MOQ Negotiable Leadtime Negotiable
Payment Options Negotiable Shipping time Negotiable

NextOneEnergy.Co.Ltd

Country / Year Established
South Korea South Korea /
Business type
Others

10

DUNS

President
SeungHee. roh
Address
#1405, Kolong Digital Tower, YangpeungRo 22Gil 21, YeongDeungPo-Gu, Seoul, South.Korea
Product Category
Electrical Components & Telecoms
No. of Total Employees
1-50
Company introduction
Next One Energy.Co.Ltd is one of Expert for Static Var compensator. 3phase 208V ~ 480V. Use SCR Switching module and support Zero crossing technology.
Main Markets

Kuwait Kuwait

Main Product

Related Products

Other buyers also search

Membership Grade

BUYER

Biz Pro VIP

SELLER

Biz Pro VIP
팝업닫기
Live Chat A new message arrives
from a business partner.

No Data

  • There is no data to load
  • Check out the My TK > My Inquiries list.
  • After agreeing to the use of the Live Chat service, the list is printed only when there is at least one history of receiving or sending a Live Chat request.

If you have not yet agreed to use the Live Chat service,

You can use the Live Chat freely after agreeing to the use of the Live Chat service.

View more
View more