Product name | High Precision Portable CT PT Analyzer 0.02% / 0.05% Ratio E | Certification | - |
---|---|---|---|
Category | Other Power Tools | Ingredients | - |
Keyword | current transformers tests , current transformer transformation ratio test , current transformer analyzer , current transformer test system | Unit Size | - |
Brand name | - | Unit Weigh | - |
origin | China | Stock | - |
Supply type | - | HS code | - |
Product Information
GF1061 portable CT PT analyzer is mainly used
for field or lab testing, it can finish the measurements (M) and protection (P)
class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini
type printer supporting field printing; supporting to use USB flash disk to
dump data. The CT PT Analyzer is the most complete and easy-to-use testing
system for protection and metering CTs according to IEEE and IEC standards.
The CT Analyzer automatically determines all
relevant current transformer values and compares the results with the selected
standard. The device evaluates the current transformer as per the IEC or IEEE
standard within seconds with the push of a button. its can test current
transformer and potential transformer ratio error and phase error, Magnetization curve etc.
It facilitates fast and economical on-site testing and calibration of metering
and protection current transformers. Manufacturers of current transformers,
high voltage transformers and switchgear also use the CT Analyzer for tests
during development and production.
Application
1. Measurement type current transformer
2. Protection type current transformer
3. GIS type current transformer
4. Bushing type current transformer
5. Zero sequence current transformer
6. Voltage transformer
MAIN FUNCTIONS
I. Current
Transformer (CT) |
II. Voltage
Transformer (PT) |
1. Magnetization curve |
1. Excitation characteristic test |
2. Transformation ratio test |
2. Transformation ratio test |
3. Polarity |
3. Polarity |
4. 5% and 10% error curve |
4. Ratio error, phase error |
5. Accuracy limiting factor (ALF) |
5. Degauss |
6. Degauss |
6. Calculation of knee point value |
7. Ratio error, phase error |
7. Actual secondary load test
(burden test) |
8. Automatic calculation of
excitation knee |
8. Resistance test |
9. Actual secondary load test
(burden test) |
|
10. Resistance test |
|
11. Secondary time constant (Ts) |
|
12. Remanence coefficient (Kr) |
|
13. Transient dimensioning factor
(Ktd) |
|
14. Peak instantaneous error (Er) |
|
15. Magnetizing inductance (LU) |
|
16. Instruments security
factor(FS) |
|
17. Composite error |
PARAMETERS
Electrical
parameters |
||
Accuracy |
0.05%, 0.02% |
|
Power supply |
AC 220V±10% or AC 120V±10%,
50/60Hz or Battery |
|
Output voltage |
0-100Vrms |
|
Output current |
0-5Arms (20A peak-value) |
|
Output power |
0-400 VA (1500 VApeak) |
|
Automatic frequency variation
range |
0.1-60Hz |
|
Equivalent excitation voltage |
≤5000V |
|
Accuracy |
≤0.5% |
|
Secondary winding DC resistance
measurement |
Range |
0.1-1000Ω |
Accuracy |
≤0.05% |
|
Secondary actual load measurement |
Range |
5VA-1000VA |
Accuracy |
≤0.5%±0.1VA |
|
CT/PT phase error measurement |
Accuracy |
±1min (typical) / 3 min
(guaranteed) |
Resolution |
0.1min |
|
CT ratio error measurement |
Range |
1-50000 |
Accuracy |
≤0.05% |
|
PT ratio error measurement |
Range |
1-10000 |
Accuracy |
≤0.05% |
|
Standards |
||
Reference standards |
GB1207-2006, GB1208-2006,
GB16847-1997 |
|
Safety standards |
GB 4793.1-2007 |
|
EMC |
EMC standard 89/336/EEC |
|
FCC Subpart B of Part 15 Class A |
||
IEC 1000-4-2 /3 /4 /6 |
||
Mechanical
parameters |
||
Overall dimension (L x W x H) (mm) |
280 x 250 x 160 |
|
Weight (kg) |
≤4 |
|
Environmental
conditions |
||
Relative humidity |
Relative humidity 5%-95% not
condensing |
|
Operating temperature |
-10°C to +50°C |
|
Storage temperature |
-20°C to +70°C |
|
Altitude |
≤1000m |
B2B Trade
Price (FOB) | Negotiable | transportation | - |
---|---|---|---|
MOQ | Negotiable | Leadtime | Negotiable |
Payment Options | D/A,L/C,T/T,Western Union | Shipping time | Negotiable |
- President
- Mr.huang
- Address
- 01117-8 Fortune Street No.67 Chaoyang Road, Chaoyang District, Beijing, China.
- Product Category
- Machinery & Parts,POS Systems
- Company introduction
-
Beijing GFUVE Electronics Co.,Ltd. was established in 2005, registered. Science, industry and trade as one of the high-tech enterprise, specializing in high voltage ammeter recorder and IEC61850 test suite software, intelligent instrument, meter test equipment, reference standard meter, electric meter-reading system, handheld terminal(PDA), POS terminal, Common Meter Reading Instrument, standard sources, phantom loads, relay test set, transformer test equipment, transducer, power meter, current transformer and the power automation products development, production, sales, And also, and foreign distributors to maintain good relations of cooperation.
Beijing GFUVE Electronics Co.,Ltd. is a leader manufacturer of energy meter test products and handheld computer in China. It is professional in energy meter test system, energy meter portable tester and related accessory. Our company is strictly according to ISO9001 standards for production, the products of quality stable and reliable.
GFUVE company has a perfect human resource system: there are more than 150 employees, all with college degree or above, and age are not more than 35 years old, The company has gathered in power system and automation, computer application, and communication technology, professional experienced technical elites to build a high quality team, realizing the rapid development of the company and the employee.
Our products are IEC standard products which are the same as Radian, MTE or Zera, and our price is very reasonable. We have exported our products to all over the world including Europe, South America, Africa, Oceania and Asia and so on.
Best quality with the best price, products customization, and professional pre-sales and after-sales technical support are our main advantages which make our successful business. Moreover, GFUVE Company also offers professional electricity product design processing services. To help customers solve the problem.
We are looking forward to receiving your inquiry in the near future. Please contact us if you have interest in our products.
In addition, professional agent required worldwide. Please join us, we will develop together.
- Main Markets
-
Australia
Colombia
France
S. Yemen
South Africa
South Korea
U.S.A
- Main Product